Absolute encoder transmission sequence – Yaskawa FSP Amplifier User Manual

Page 152

Advertising
background image

FSP Amplifier User’s Manual

Chapter 5: Parameter Settings and Functions

5-85

The final absolute data P

M

can be found by using the following formulas:

Forward rotation
mode:

P

E

= M x R + P

O

P

M

= P

E

– P

S

Reverse rotation
mode:
(Pn0000.0 = 1)

P

E

= -(M x R) + P

O

P

M

= P

E

– P

S

Where: P

E

= The current value read by the encoder.

M = The multi-turn data (rotation count data).

P

O

= The number of initial incremental pulses.

P

S

= The number of initial incremental pulses read at setup.

(This is saved and controlled by the host controller).

P

M

= The current value required for the user’s system.

R = The number of pulses per encoder revolution.

(Pulse count after dividing by the value of Pn201)

„

Absolute Encoder Transmission Sequence

1. Set the SEN signal at high level.
2. After 100 ms, set the system to serial data reception-waiting-state.

Clear the incremental pulse up/down counter to zero.

3. Receive eight bytes of serial data.
4. The system enters a normal incremental operation state approximately

50 ms after the last serial data is received.