FSP Amplifier User’s Manual

Chapter 7: Using the Panel Operator

7-30

7.2.9. Initializing Parameter Settings

This function is used to reset all parameters to the default settings (standard
factory settings).

IMPORTANT

Initialize the parameter settings with the servo OFF.

After performing the procedure, cycle the power to reset all the
parameters to the default settings.

Follow the procedure below to initialize parameter settings.
1.

Press the MODE/SET key to select the Auxiliary Function mode.

2.

Press the Up Arrow or Down Arrow key to select function Fn005.

3.

Press the DATA/SHIFT key for a minimum of one second, and the

display will be as shown below.

4.

Press the MODE/SET key, and the display will be as shown below.

The parameters will be initialized.

Flashing during

initialization

End

Flashing for
one second

5.

Press the DATA/SHIFT key for a minimum of one second to return to

the Auxiliary Function mode display.

This completes the initialization of parameter settings.

Note: Parameters will not be initialized by pressing the DSPL/SET or MODE/SET key with the servo ON. Turn

the power OFF and then back ON after initialization.