FSP Amplifier User’s Manual

Chapter 7: Using the Panel Operator

7-30

7.2.9. Initializing Parameter Settings

This function is used to reset all parameters to the default settings (standard
factory settings).

IMPORTANT

• Initialize the parameter settings with the servo OFF.

•

After performing the procedure, cycle the power to reset all the
parameters to the default settings.

Follow the procedure below to initialize parameter settings.
1.

Press the MODE/SET key to select the Auxiliary Function mode.

2.

Press the Up Arrow or Down Arrow key to select function Fn005.

3.

Press the DATA/SHIFT key for a minimum of one second, and the

display will be as shown below.

4.

Press the MODE/SET key, and the display will be as shown below.

The parameters will be initialized.

Flashing during

initialization

End

Flashing for
one second

5.

Press the DATA/SHIFT key for a minimum of one second to return to

the Auxiliary Function mode display.

This completes the initialization of parameter settings.

Note: Parameters will not be initialized by pressing the DSPL/SET or MODE/SET key with the servo ON. Turn

the power OFF and then back ON after initialization.