Chapter 9: Inspection, Maintenance, and Troubleshooting

9-9

„

A.10: Overcurrent or Heat Sink Overheated

Display and Outputs

Alarm Outputs

Alarm Code Output

ALO1 ALO2

ALO3

ALM Output

ON OFF

OFF

OFF

Note: OFF: Output transistor is OFF (alarm state).

ON: Output transistor is ON.

Status and Remedy for Alarm

During servomotor

operation

At power ON.

When Servo ON

(S-ON) signal is

turned ON.

A, B, D,
E, F, G

C, D

C

Cause of the Problem

Solution

A

Shorted wiring between servo
amplifier and servomotor.

Check and correct wiring.

B

Shorted servomotor U, V, or W
phase.

Replace servomotor.

C

Defective circuit board (1PWB)
Defective power transistor.

Replace servo amplifier.

D

Defective current feedback circuit,
power transistor, DB circuit, or
circuit board.

Replace servo amplifier.

E

Ambient temperature of the servo
amplifier greater than 55°C.

Alter conditions so that the ambient
temperature is below 55°C.

F

Inadequate airflow around the heat
sink.

Providing sufficient space as
specified.

G

Fan stopped.

Replace servo amplifier.

H

Servo amplifier is operating under
an overload.

Reduce load.

Note:

Problems E to H can occur in a servo amplifier with a capacity of 1.5 to 5 kW, and all 400 V

models.