Jog operation, Caution – Yaskawa FSP Amplifier User Manual
Page 209

FSP Amplifier User’s Manual
Chapter 7: Using the Panel Operator
7-18
7.2.2. JOG Operation
CAUTION
• Forward Run Prohibited (/P-OT) and Reverse Run Prohibited (/N-OT)
signals are not effective during JOG operations using function Fn002.
Operation from the digital operator allows the servo amplifier to run the
motor. This allows checking the motor’s rotation direction and speed
setting rapidly during machine setup and testing, saving the time and
trouble of connecting to a host controller.
For the motor speed setting procedure, refer to 7.1.5 Operation in
Parameter Setting Mode and 5.3.2 JOG Speed.
FSP Amplifier
The operating procedure using the digital operator is described on the
following pages.
1. Press the MODE/SET key to select Fn002 in the Auxiliary Function
mode.
2. Press the DATA/SHIFT key for a minimum of one second to select the
Panel Operator Operation mode. Operation is now possible using the
panel operator.