A.30: regenerative error detected – Yaskawa FSP Amplifier User Manual

Page 275

Advertising
background image

FSP Amplifier User’s Manual

Chapter 9: Inspection, Maintenance, and Troubleshooting

9-10

„

A.30: Regenerative Error Detected

Display and Outputs

Alarm Outputs

Alarm Code Output

ALO1 ALO2

ALO3

ALM Output

ON ON

OFF

OFF

Note: OFF: Output transistor is OFF (alarm state).

ON: Output transistor is ON.

Status and Remedy for Alarm

During servomotor

operation

About 1s after

main circuit power

is turned ON.

When the control

power is turned ON.

A, B

D

A, B, C

Cause of the Problem

Solution

A

Malfunctioning regenerative transistor.

Replace servo amplifier.

B

Regenerative resistor is open.

Replace servo amplifier or
regenerative resistor.

C

Disconnected regenerative unit (for an
external regenerative resistor).

Check the wiring of the external
regenerative resistor.

D

Defective servo amplifier.

Replace servo amplifier.