Examples of input signal allocation – Yaskawa FSP Amplifier User Manual

Page 115

Advertising
background image

FSP Amplifier User’s Manual

Chapter 5: Parameter Settings and Functions

5-48

„

Examples of Input Signal Allocation

The procedure used to allocate sequence input signals is described using
the /S-ON signal as a typical example.

Pn50A.1

Setting

Description

0

Inputs the /S-ON signal from the SI0 (CN1-40) input terminal.

1

Inputs the /S-ON signal from the SI1 (CN1-41) input terminal.

2

Inputs the /S-ON signal from the SI2 (CN1-42) input terminal.

3

Inputs the /S-ON signal from the SI3 (CN1-43) input terminal.

4

Inputs the /S-ON signal from the SI4 (CN1-44) input terminal.

5

Inputs the /S-ON signal from the SI5 (CN1-45) input terminal.

6

Inputs the /S-ON signal from the SI6 (CN1-46) input terminal.


Signal polarity:
Normal.
Servo ON signal
is valid when low
(ON)

7

Sets /S-ON signal so that it is always valid.

8

Sets /S-ON signal so that it is always invalid.

Set the Servo-ON
signal (/S-ON) so
that it is always
valid or always
invalid.

9

Inputs the S-ON signal from the SI0 (CN1-40) input terminal.

A

Inputs the/S-ON signal from the SI1 (CN1-41) input terminal.

B

Inputs the S-ON signal from the SI2 (CN1-42) input terminal.

C

Inputs the S-ON signal from the SI3 (CN1-43) input terminal.

D

Inputs the S-ON signal from the SI4 (CN1-44) input terminal.

E

Inputs the S-ON signal from the SI5 (CN1-45) input terminal.

F

Inputs the/S-ON signal from the SI6 (CN1-46) input terminal.


Signal polarity:
Inversion.
Valid at OFF
(H level) with
Servo
ON signal

As shown in the table above, the /S-ON signal can be allocated to any input
terminal from SI0 to SI6. /S-ON is always input when Pn50A.1 is set to 7,
and an external signal line would therefore not be needed because the servo
amplifier will determine whether the servo is ON or OFF.
The /S-ON signal is not used when Pn50A.1 is set to 8. This setting is
meaningful only in the following instances.
• When the factory set input signal is to be replaced by another input

signal.

• The signal must be left ON (low level) during normal operation to

make the signal valid when OFF (high level) when forward run prohibit
(P-OT) and reverse run prohibit (N-OT) are input. The input terminal
signal line must be left ON even in system configurations that do not
require this signal. Unnecessary wiring can be eliminated by setting
Pn50A.1 to 8.

• By setting 9 to F, the signal polarity can be reversed.

Note:

Several signals can be allocated to the same input circuit.
When the servo is ON, the forward run prohibit or reverse run prohibit signal is used.
At a setting with inverted polarity, the failed safe operation may not be possible in the case of signal line
disconnection.

Advertising