B.1. Wiring Precautions

To ensure safe and stable operation, always observe the following wiring
precautions:

1. Always use the following cables for reference input and encoder

wiring.

Cable

Type

Yaskawa

Drawing Number

Maximum Allowable Length

Reference Input

Twisted pair wires

JZSP-CKI01

118 in (3 m)

JZSP-CMP00

SGMAH, SGMPH

787 in (20 m)

Encoder

Multi-conductor
shielded twisted air
wire

JZSP-CMP02

SGMGH, SGMSH

1969 in (50 m)

• Trim off the excess portion of the cable to minimize the cable

length.

2. For a ground wire use as large a wire as possible: AWG14

(2.0 mm

2

) or larger.

• At least class-3 ground (100 Ω maximum) is recommended.
• Ground to one point only.
• If the motor is insulated from the machine, ground the motor

directly.

3. Do not bend or apply tension to cables.

The conductor of a signal cable is very thin (0.0079 to 0.012 in. (0.2 to
0.3 mm)), handle the cables with care.

4. Use a noise filter to prevent noise interference.

• If the equipment is to be used near private houses or may receive

noise interference, install a noise filter on the input side of the
power supply line.

• Since this servo amplifier is designed as an industrial device, it

provides no mechanism to prevent noise interference.