Servo amplifier orientation, Cooling, Side-by-side installation – Yaskawa FSP Amplifier User Manual
Page 25: Environmental conditions in the control panel

FSP Amplifier User’s Manual
Chapter 2: Installation
2-4
Servo Amplifier Orientation
Install the servo amplifier perpendicular to the wall so the front panels’
connectors face outward.
Cooling
As shown in the figure, allow sufficient space around each servo amplifier
for cooling by cooling fans or natural convection.
Side-by-side Installation
When installing servo amplifiers side-by-side as shown in the figure, allow
at least 0.39 in (10 mm) between and at least 1.97 in (50 mm) above and
below each servo amplifier. Install cooling fans above the servo amplifiers
to avoid excessive temperature rise and to maintain even temperature inside
the control panel.
Environmental Conditions in the Control
Panel
• Ambient
Temperature:
0
to
55°C
• Humidity:
90%
RH
or
less
• Vibration:
0.5
G
(4.9
m/s
2
)
• Condensation and Freezing:
None
• Ambient Temperature for Long-term Reliability: 45°C max.