Yaskawa FSP Amplifier User Manual

Page 129

Advertising
background image

FSP Amplifier User’s Manual

Chapter 5: Parameter Settings and Functions

5-62

The user must provide a suitable external I/O power supply separately
because there is no internal 24 V power supply in the servo amplifier.
The use of the photocoupler output signals is described below.

Output Ö ALM+ CN1-31

Servo Alarm Output

Speed, Torque, Position
Control, and Programming

Output Ö ALM- CN1-32

Signal Ground for Servo Alarm Output

Speed, Torque, Position
Control, and Programming

These alarms are output when a servo amplifier alarm is detected.

ALM output

Turns power OFF

Alarm

detection

FSP Amplifier

Form an external circuit so that this alarm output (ALM) turns OFF the
servo amplifier.

State Status Result

ON

Circuit between CN1-31 and 32 is closed, and
CN1-31 is at low level.

Normal state

OFF

Circuit between CN1-31 and 32 is open, and
CN1-31 is at high level.

Alarm state

Alarm codes ALO1, ALO2 and ALO3 are output to indicate each alarm
type.
The use of open-collector output signals ALO1, ALO2, and ALO3 is
described below.

Output Ö ALO1 CN1-37

Alarm Code Output

Speed, Torque, Position
Control, and Programming

Output Ö ALO2 CN1-38

Alarm Code Output

Speed, Torque, Position
Control, and Programming

Output Ö ALO3 CN1-39

Alarm Code Output

Speed, Torque, Position
Control, and Programming

Output Ö /SG CN1-1

Signal Ground for Alarm Code Output

Speed, Torque, Position
Control, and Programming

These signals output alarm codes to indicate the type of alarm detected by
the servo amplifier. Use these signals to display alarm codes at the host
controller. See 9.2.3 Alarm Display Table for more on the relationship
between alarm display and alarm code output.
When a servo alarm (ALM) occurs, eliminate the cause of the alarm and set
the following /ALM-RST input signal to high level (ON) to reset the alarm.

Input Ö /ALM-RST CN1-44

Alarm Reset

Speed, Torque, and Position
Control

Advertising