FSP Amplifier User’s Manual

Chapter 5: Parameter Settings and Functions

5-75

Series

Allowable Frequencies in Regeneration Mode (r/min)

Voltage

Capacity

Symbol

03

05

08

09

10

13

15

20

30

50

SGMAH-ٱA

— — 89 — — — — — — —

SGMPH-ٱA

— — 29 — — — 17 — — —

SGMGH-ٱA

— 34 — 13 — 10 — 12 8 —

200 V

SGMSH-ٱA

— — — — 39 — 31 48 20 —

SGMGH-ٱD

— 42 — 15 — 10 — 12 8 —

SGMSH-ٱD

— — — — 47 — 31 48 20 22

400 V

SGMUH-ٱD

— — — — 27 — 19 — 13 —

Operating Conditions for Allowable Regenerative
Frequency Calculation

Use the following equation to calculate the allowable frequency for
regeneration mode operation.

Allowable frequency =

n)

(1

only

servomotor

for

frequency

Allowable

+

x

2

used

speed

Rotation

speed

rotation

.

Max

⎟⎟

⎜⎜

Minute

Cycles

Where: n = J

L

/J

M

J

L

: Motor axis conversion load inertia [oz·in·s

2

(kg·m

2

)]

J

M

: Servomotor rotary inertia [oz·in·s

2

(kg·m

2

)]