FSP Amplifier User’s Manual

Chapter 5: Parameter Settings and Functions

5-16

This circuit uses the 12 V power supply built into the servo amplifier. The
input is not isolated in this case.

Ω

Ω

FSP Amplifier

Note: The noise margin of the input signal will decrease if the reference pulse is provided by an open-collector

output. Set parameter Pn200.3 to 1 if the position drifts due to noise.

„

Selecting a Reference Pulse Form

Use the following parameters to select the reference pulse form used.

Ö

Input PULS CN1-7

Reference Pulse Input

Position Control

Ö

Input /PULS CN1-8

Reference Pulse Input

Position Control

Ö

Input SIGN CN1-11

Reference Code Input

Position Control

Ö

Input /SIGN CN1-12

Reference Code Input

Position Control


The servomotor only rotates at an angle proportional to the input pulse.

Parameter Signal

Setting

Control

Mode

Pn200.0

Reference Pulse Form

Default Setting: 4

Position Control and
Programming

Set reference pulse form input to the servo amplifier from the host
controller.

Note: This function works only with a Pulse Reference, not with a Serial Command.

CN1-7

CN1-11

PULSE

SIGN

Position

reference

pulse

FSP Amplifier

Host

controller

Since the reference pulse form can be selected from among those listed on
the next page, set one according to host controller specifications.