Chapter 9: Inspection, Maintenance, and Troubleshooting

9-35

„

A.F1: Power Line Open Phase

Display and Outputs

Alarm Outputs

Alarm Code Output

ALO1 ALO2

ALO3

ALM Output

ON ON

OFF

OFF

Note: OFF: Output transistor is OFF (alarm state).

ON: Output transistor is ON.

Status and Remedy for Alarm

When the main
circuit's power supply
is turned ON.

When the control
power is turned ON.

A, B

C

Cause of the Problem

Solution

A

One phase (L1, L2, or L3) of the main
circuit power supply is disconnected.

•

Check power supply.

•

Check wiring of the main
circuit power supply.

•

Check MCCB, noise filter,
magnetic contactor.

B

There is one phase where the line
voltage is low.

Check power supply.

C

Servo amplifier defective.

Replace servo amplifier.

Note: A and B tend to occur in a servo amplifier with a capacity of 500 W or higher.