A.f1: power line open phase – Yaskawa FSP Amplifier User Manual

Page 300

Advertising
background image

FSP Amplifier User’s Manual

Chapter 9: Inspection, Maintenance, and Troubleshooting

9-35

„

A.F1: Power Line Open Phase

Display and Outputs

Alarm Outputs

Alarm Code Output

ALO1 ALO2

ALO3

ALM Output

ON ON

OFF

OFF

Note: OFF: Output transistor is OFF (alarm state).

ON: Output transistor is ON.

Status and Remedy for Alarm

When the main
circuit's power supply
is turned ON.

When the control
power is turned ON.

A, B

C

Cause of the Problem

Solution

A

One phase (L1, L2, or L3) of the main
circuit power supply is disconnected.

Check power supply.

Check wiring of the main
circuit power supply.

Check MCCB, noise filter,
magnetic contactor.

B

There is one phase where the line
voltage is low.

Check power supply.

C

Servo amplifier defective.

Replace servo amplifier.

Note: A and B tend to occur in a servo amplifier with a capacity of 500 W or higher.