FSP Amplifier User’s Manual

Chapter 9: Inspection, Maintenance, and Troubleshooting

9-34

„

A.d0: Position Error Pulse Overflow

Display and Outputs

Alarm Outputs

Alarm Code Output

ALO1 ALO2

ALO3

ALM Output

ON ON

OFF

OFF

Note: OFF: Output transistor is OFF (alarm state).

ON: Output transistor is ON.

Status and Remedy for Alarm

During servomotor operation.

At power ON.

A

E

During high speed
rotation.

When a long reference is
entered during normal
operation.

When a properly entered
reference pulse does not
generate a feedback
pulse.

A

B, C, D

E

Cause of the Problem

Solution

A

Servomotor wiring incorrect or
poor connection

Check wiring and connectors at encoder.

B

Servo amplifier was not
correctly adjusted.

Increase speed loop gain (Pn100) and
position loop gain (Pn102).

C

Motor load was excessive.

Reduce load torque or inertia. If problem
persists, replace with a larger capacity
motor.

D

Position reference pulse
frequency was too high.

Increase or decrease reference pulse
frequency.

Add smoothing function.

Correct electronic gear ratio.

E

Circuit board (1PWB) defective.

Replace servo amplifier.