Yaskawa SGDS Sigma III Servo Amplifier User Manual

Page 124

Advertising
background image

5.6 Others

5-21

2. Separate the noise filter ground wire from the output lines.

Do not accommodate the noise filter ground wire, output lines and other signal lines in the same duct or
bundle them together.

3. Connect the noise filter ground wire directly to the ground plate.

Do not connect the noise filter ground wire to other ground wires.

4. When grounding a noise filter inside a unit:

If a noise filter is located inside a unit, connect the noise filter ground wire and the ground wires from
other devices inside the unit to the ground plate for the unit first, then ground these wires.

The ground wire
can be close to
input lines.

Noise

Filter

Noise

Filter

Box

Box

Incorrect

Correct

Shielded
ground wire

Thick and
short

Noise
Filter

Noise
Filter

Box

Box

SERVOPACK

SERVOPACK

SERVOPACK

SERVOPACK

Incorrect

Correct

Noise
Filter

Unit

Ground

Box

SERVOPACK

SERVOPACK

Advertising