6 MECHATROLINK II Communications

6.3.8 Start Synchronous Communications (SYNC_SET: 0DH)

6-14

6.3.8 Start Synchronous Communications (SYNC_SET: 0DH)

Byte

SYNC_SET

Description

Command

Response

1

0DH

0DH

Processing
classifications

Network com-
mand group

Synchronization
classifications

Asynchronous

2

ALARM

Processing time

Transmission
cycle or more

Subcommand

Cannot be used

3

STATUS

• Starts synchronous communications. Switches from phase 2 to phase 3.
• Processing is completed at the WDT changing edge.

However, if WDT errors are being masked by parameter Pn800.0, processing
is completed when this command is received.

• During phase 1, a MECHATROLINK II command warning1 (A.95A) will

occur and the command will be ignored.

• During phase 3, the command will be ignored (without a warning).
• The SERVOPACK will change to Servo OFF if this command is received.
• At the occurrence of the following alarms, this command must be transmitted

to restart synchronous communications.
- MECHATROLINK II Synchronization Error (A.E50)
- MECHATROLINK II Synchronization Failure (A.E51)
- MECHATROLINK II Communications Error (A.E60)
- MECHATROLINK II Transmission Cycle Error (A.E61)