8.6 Servo Gain Adjustment Functions

8-25

Using the Torque Reference Level to Switch Modes (Factory Setting)

With this setting, the speed loop is switched to P control
when the value of torque reference input exceeds the torque
set in parameter Pn10C. The factory default setting for the
torque reference detection point is 200

% of the rated torque

(Pn10C = 200).

Operating Example

If the mode switch function is not being used and the SERVOPACK is always operated with PI control, the speed of the
motor may overshoot or undershoot due to torque saturation during acceleration or deceleration. The mode switch function
suppresses torque saturation and eliminates the overshooting or undershooting of the motor speed.

Using the Speed Reference Level to Switch Modes

With this setting, the speed loop is switched to P control when the value
of speed reference input exceeds the speed set in parameter Pn10D.

Operating Example

In this example, the mode switch is used to reduce the settling time. It is necessary to increase the speed loop gain to reduce
the settling time. Using the mode switch suppresses overshooting and undershooting when speed loop gain is increased.

Motor speed

Reference speed

Speed

Torque Reference

+Pn10C

Torque Reference 0

- Pn10C

PI Control

PI Control

PI

P

P

Motor
speed

Time

Overshoot

Undershoot

Motor
speed

Time

Without mode Switching

Without mode Switching

Speed reference

Speed

Pn10D

Motor
speed

Time

P Control

PI

PI Control

Increase speed loop gain

Overshoot

Undershoot

Motor
speed

Time

Setting time

Motor
speed

Motor speed

Speed reference

Long Setting Time

Motor
speed

Without mode Switching

Without mode Switching