2 molded-case circuit breaker and fuse capacity, 2 mo – Yaskawa SGDS Sigma III Servo Amplifier User Manual

Page 54

Advertising
background image

2.5 Selecting Peripheral Devices

2-25

2.5.2 Molded-case Circuit Breaker and Fuse Capacity

* 1. Nominal value at the rated load. The specified derating is required to select an appropriate

fuse capacity.

* 2. Cutoff characteristics (25

°

C): 200% two seconds min. and 700% 0.01 seconds min.

Note: Do not use a fast-acting fuse. Because the SERVOPACK’s power supply is a capacitor

input type, a fast-acting fuse may blow when the power is turned ON.

The SGDS SERVOPACK does not include a protective grounding circuit. Install a ground-fault protector to
protect the system against overload and short-circuit or protective grounding combined with the molded-
case circuit breaker.

Main Circuit

Power Supply

Servo Amp. Model

Power Supply Capacity

per Servo Amplifier

(kVA)

Current Capacity of

Molded-case Circuit Breaker or Fuse

(A

rms

)

*1,*2

(Refer to 4.4.5)

Capacity

(kW)

SGDS-

Single-phase
100 V

0.05

A5F

0.25

4

0.10

01F

0.40

0.20

02F

0.60

6

0.40

04F

1.2

12

Single-phase
200 V

0.05

A5A

0.25

4

0.10

01A

0.40

0.20

02A

0.75

0.40

04A

1.2

8

0.80

08A

2.2

16

Three-phase
200 V

0.45

05A

1.4

4

1.0

10A

2.3

7

1.5

15A

3.2

10

2.0

20A

4.3

12

3.0

30A

5.9

17

IMPORTANT