3 position loop gain, 3 position loop gain -21 – Yaskawa SGDS Sigma III Servo Amplifier User Manual

Page 248

Advertising
background image

8.5 Manual Tuning

8-21

• Servo Gain Manual Tuning

8.5.3 Position Loop Gain

If the position loop gain (Pn102) can not be set high in the mechanical system, an overflow alarm may occur during high
speed operation. In this case, increase the values in the following parameter to suppress detection of the overflow alarm.

Step

Explanation

1

Increase the speed loop gain (Pn100) to within the range so that the machine does not vibrate. At the
same time, decrease the speed loop integral time constant (Pn101).

2

Adjust the 1st Step 1st torque reference filter time constant (Pn401) so that no vibration occurs.

3

Repeat the steps 1 and 2. Then reduce the value for 10 to 20%.

4

For the position control, increase the position loop gain (Pn102) to within the range so that the machine
does not vibrate.

Pn102

Position Loop Gain (Kp)

Setting Range

Setting Unit

Factory Setting

Setting Validation

1.0 to 2,000.0/s

0.1/s

40.0/s

Immediately

The responsiveness of the position loop in the SERVOPACK is determined by the position loop gain. The responsiveness
increases and the positioning time decreases when the position loop gain is set to a higher value. In general, the position
loop gain cannot be set higher than natural vibrating frequency of the mechanical system, so the mechanical system must be
made more rigid to increase its natural vibrating frequency and allow the position loop gain to be set to a high value.

Position

INFO

Pn520

Excessive Position Error Alarm Level

Setting Range

Setting Unit

Factory Setting

Setting Validation

1 to 1,073,741,823

(2

30

-1) reference units

Reference units

262,144 reference unit

Immediately

This parameter’s new setting must satisfy the following condition.

Position

Pn520

Pn102

2.0

Max. feed speed (reference units/s) ×

Advertising