7 Operation

7.3.3 Software Limit Settings

7-12

(2) Software Limit Check using References

Enable or disable software limit checks when target position references such as POSING or INTERPOLATE are
input. When the input target position exceeds the software limit, a deceleration stop will be performed from the
software limit set position.

(3) Software Limit Setting

Set software limits in the positive and negative directions.
Because the limit zone is set according to the (+) or (-) direction, the negative (

-

) limit must be less than the

positive (+) limit.

The negative limit must be less than the positive limit.

Parameter

Description

Pn801

n.

0

No software limit check using references. (Factory setting)

n.

1

Software limit check using references.

Pn804
Pn805

Forward Software Limit

Setting Range

Setting Unit

Factory Setting

Setting Validation

-1073741823 to 1073741823

1 Reference Unit

8192

∗99999

Immediately

Pn806
Pn807

Reverse Software Limit

Setting Range

Setting Unit

Factory Setting

Setting Validation

-1073741823 to 1073741823

1 Reference Unit

8192

∗99999

Immediately

Position

Position