10.1 Troubleshooting

10-5

A.CF2

Fully-closed Serial
Converter Unit
Communications Error
(Timer Stopped)

Communication of fully-closed serial converter unit is faulty.

DB stop

N/A

H

A.d00

Position Error Pulse
Overflow

Position error pulse exceeded parameter (Pn520).

DB stop

Available

A.d01

Position Error Pulse
Overflow Alarm
at Servo ON

When the servo turns ON, the position error pulses exceeded
the parameter setting (Pn526).

DB stop

Available

A.d02

Position Error Pulse
Overflow Alarm by Speed
Limit at Servo ON

If the servo turns ON with position error pulses accumulated,
the speed is limited by Pn529. In this state, the reference
pulse was input without resetting the speed limit, and the
position error pulses exceeds the value set for the parameter
Pn520.

Zero speed

stop

Available

A.d10

Motor-Load Position
Error Pulse Overflow

Position error pulse between motor and load is too large.

Zero speed

stop

Available

A.E00

COM Alarm 0

SERVOPACK “COM error 0.”

Zero speed

stop

Available

A.E01

COM Alarm 1

SERVOPACK “COM error 1.”

Zero speed

stop

Available

A.E02

COM Alarm 2

SERVOPACK “COM error 2.”

Zero speed

stop

Available

A.E07

COM Alarm 7

SERVOPACK “COM error 7.”

Zero speed

stop

N/A

A.E40

MECHATROLINK II
Transmission Cycle
Setting Error

Transmission cycle setting of MECHATROLINK II is
incorrect.

Zero speed

stop

Available

A.E50

MECHATROLINK II
Synchronization Error

Synchronization error during MECHATROLINK II
communications.

Zero speed

stop

Available

A.E51

MECHATOLINK II
Synchronization Failed

Synchronization error during MECHATROLINK II
communications.

A.E60

MECHATROLINK II
Communications Error

Continuous communications error during
MECHATROLINK II communications.

Zero speed

stop

Available

A.E61

MECHATROLINK II
Transmission Cycle Error

Transmission cycle error during MECHATROLINK II
communications.

Zero speed

stop

Available

A.EA0

DRV Alarm 0

SERVOPACK “DRV error 0.”

DB stop

N/A

A.EA1

DRV Alarm 1

SERVOPACK “DRV error 1.”

DB stop

N/A

A.EA2

DRV Alarm 2

SERVOPACK “DRV error 2.”

Zero speed

stop

Available

A.ED0

Internal Command Error

Command error in the SERVOPACK.

Zero speed

stop

Available

A.F10

Power Line Open Phase

One phase is not connected in the main power supply.

Zero speed

stop

Available

CPF00

Digital Operator
Transmission Error

Digital operator (JUSP-OP05A) fails to communicate with
SERVOPACK (e.g., CPU error).

N/A

CPF01

N/A

A.

− −

Not an error

Normal operation status

L

Table 10.1 Alarm Display Table (Cont’d)

Alarm

Display

Alarm Name

Meaning

Servomo-

tor Stop

Method

Alarm
Reset

Servo
Alarm

(ALM)

Output