8 Adjustments

8.6.8 Less Deviation Control

8-40

8.6.8 Less Deviation Control

Less Deviation Control can provide shorter settling times and lower locus tracking errors by reducing the
position error as much as possible for the position control mode. There are two kinds of Less deviation control:
Basic Less deviation and Less Deviation control with reference filter. Operation can be adjusted easily with
utility function Fn015 (One-parameter Tuning for Less Deviation Control.) If higher performance operation is
required, the settings can be fine-tuned with the parameters.

Example Response Waveforms for Less Deviation Control

(1) Related Parameters

Example Response Waveform

for Less Deviation Control

Example Response Waveform

for Less Deviation Control with Reference Filter

Position

Position

Error

Time

Time

Position reference

(Host reference)

Using Less Deviation

Control

Using Less

Deviation Control

Not using Less

Deviation Control

Not using Less

Deviation Control

Position

Position
Error

Time

Time

Position reference
(Host reference)

Using Less Deviation Control
with Reference filter

Using Less Deviation Control
with Reference filter

Not using Less Deviation Control
with Reference Filter

Not using
Less Deviation Control

Pn119

Reference Filter Gain

Setting Range

Setting Unit

Factory Setting

Setting Validation

1.0 to 2,000.0 /s

0.1 /s

50.0 /s

Immediately

Pn11A

Reference Filter Gain Compensation

Setting Range

Setting Unit

Factory Setting

Setting Validation

50.0% to 200.0%

0.1%

100%

Immediately

Pn11E

Reference Filter Bias (Forward)

Setting Range

Setting Unit

Factory Setting

Setting Validation

0.0% to 1,000.0%

0.1%

100%

Immediately

Pn144

Reference Filter Bias (Reverse)

Setting Range

Setting Unit

Factory Setting

Setting Validation

0.0% to 1,000.0%

0.1%

100%

Immediately

Pn1A0

Servo Rigidity

Setting Range

Setting Unit

Factory Setting

Setting Validation

1% to 500%

1%

60%

Immediately

Pn1A1

Servo Rigidity #2

Setting Range

Setting Unit

Factory Setting

Setting Validation

1% to 500%

1%

60%

Immediately

Position

Position

Position

Position

Position

Position