10.1 Troubleshooting

10-3

10.1.2 Alarm Display Table

Alarm display, names, and meanings are shown in table 10.1.
If an alarm occurs, the servomotor can be stopped by doing either of the following operations.

• DB STOP: Stops the servomotor immediately using the dynamic brake.
• ZERO-SPEED STOP: Stops the servomotor by setting the speed reference to “0.”

Table 10.1 Alarm Display Table

Alarm

Display

Alarm Name

Meaning

Servomo-

tor Stop

Method

Alarm
Reset

Servo
Alarm

(ALM)

Output

A.020

Parameter Checksum
Error 1

The data of the parameter in the SERVOPACK is incorrect.

DB stop

N/A

H

A.021

Parameter Format Error 1

The data of the parameter in the SERVOPACK is incorrect.

DB stop

N/A

A.022

System Parameter
Checksum Error 1

The data of the parameter in the SERVOPACK is incorrect.

DB stop

N/A

A.023

Parameter Password Error
1

The data of the parameter in the SERVOPACK is incorrect.

DB stop

N/A

A.02A

Parameter Checksum
Error 2

The data of the parameter in the SERVOPACK is incorrect.

DB stop

N/A

A.02b

System Parameter
Checksum Error 2

The data of the parameter in the SERVOPACK is incorrect.

DB stop

N/A

A.030

Main Circuit Detector
Error

Detection data for power circuit is incorrect.

DB stop

Available

A.040

Parameter Setting Error 1

The parameter setting is outside the allowable setting range.

DB stop

N/A

A.04A

Parameter Setting Error 2

The parameter setting is outside the allowable setting range.

DB stop

N/A

A.041

Dividing Pulse Output
Setting Error

The PG dividing pulse setting (Pn212) is outside the
allowable setting range or not satisfies the setting conditions.

DB stop

N/A

A.050

Combination Error

SERVOPACK and servomotor capacities do not match each
other.

DB stop

Available

A.100

Overcurrent or Heat Sink
Overheated

An overcurrent flowed through the IGBT.
Heat sink of SERVOPACK was overheated.

DB stop

N/A

A.300

Regeneration Error
Detected

Regenerative circuit or regenerative resistor is faulty.

DB stop

Available

A.320

Regenerative Overload

Regenerative energy exceeds regenerative resistor capacity.

Zero speed

stop

Available

A.330

Main Circuit Power
Supply Wiring Error

The power supply to the main circuit does not match the
parameter Pn001 setting.

DB stop

Available

A.400

Overvoltage

Main circuit DC voltage is excessively high.

DB stop

Available

A.410

Undervoltage

Main circuit DC voltage is excessively low.

Zero speed

stop

Available

A.510

Overspeed

The motor speed is excessively high.

DB stop

Available

A.511

Dividing Pulse Output
Overspeed

The motor speed upper limit of the set PG dividing pulse
(Pn212) is exceeded.

DB stop

Available

A.520

Vibration Alarm

Vibration at the motor speed was detected.

DB stop

Available

A.710

Overload: High Load

The motor was operating for several seconds to several tens
of seconds under a torque largely exceeding ratings.

Zero speed

stop

Available

A.720

Overload: Low Load

The motor was operating continuously under a torque largely
exceeding ratings.

DB stop

Available

A.730

Dynamic Brake Overload

When the dynamic brake was applied, rotational energy
exceeded the capacity of dynamic brake resistor.

DB stop

Available

A.740

Overload of Surge
Current Limit Resistor

The main circuit power was frequently turned ON and OFF.

DB stop

Available

A.7A0

Heat Sink Overheated

The heat sink of SERVOPACK overheated.

Zero speed

stop

Available