4.3 CPU Modules

— 4-51 —

Item

Specifications

Timers

1) Timing method:

Increment method

2) Types:

ON-delay, OFF-delay

3) Number of timers:

4,914 timers max.

4) Timing unit and range:

Name

Unit

Range

1-s Timer

0.1-s Timer

0.01-s Timer

0.001-s Timer

1 s

0.1 s

0.01 s

0.001 s

1 to 65535 s

0.1 to 6553.5 s

0.01 to 655.35 s

0.001 to 65.535 s

5) External setting:

Possible

6) Power interruption preservation: Possible

Counters

1) Types:

Up Counter, Down Counter

2) Number of counters:

4,914 counters max.

3) Counter range:

1 to 65,535

4) External setting:

Possible

5) Power interruption preservation: Possible

Maximum capacity of data

register

1) When the number of coils and relays is the default value, the following condition

must be met:
(Number of holding registers) + (Number of constant registers) + (Number of link
registers) ≤ 25,998

2) The maximum value of each reference can be freely set within the above limit from

the Programming Panel (Unit: word (1 word = 16 bit)).

Register

Setting range

Setting unit

Defaults

Example 1

Example 2

Holding

registers

1 to 25,995

1

9,999

19,854

25,995

Constant

registers

1 to 4,096

1

4,096

4,096

1

Link

registers

2 to 4,096

1,024

2,048

2,048

0

Memory back-up

D

Back-up range:

1) Program memory

2) Data memory

D

Backup method

1) One lithium battery

2) Five year warranty on battery (25 _C)

D

Back-up time
The total memory back-up time is 1 year (25 _C)

4