Yaskawa MEMOCON GL120 User Manual

Page 298

Advertising
background image

System Components: Functions and Specifications

4.6.3 Pulse Catch Module cont.

— 4-242 —

2) Performance Specifications

The following table shows the performance specifications of the Pulse Catch Module.

Table 4.100 Performance Specifications of Pulse Catch Module

Items

Specifications

Pulse Catch

Function

No. of Input

Circuits

16

Function

Minimum ON

Signal Width

1) With 8 Count Mode channels: 1 ms

2) With 16 Count Mode channels: 2 ms

Sixteen points can be used to catch pulses when either 8 or 16
Count Mode channels are specified.

Internal

Control

Signals

The following signals can be output to the Pulse Catch and
Counter Module from the ladder logic program.

RUN enable:
External input is enabled on the Pulse Catch and Counter Module
while this signal is ON. A signal can be set for every external input
circuit.

Counter

Function

No. of Input

Channels

16 channels (max.)

1) With 8 Count Mode channels: 8 channels max.

2) With 16 Count Mode channels: 16 channels max.

Maximum

Input Signal

Frequency

1) With 8 Count Mode channels: 500 Hz

2) With 16 Count Mode channels: 250 Hz

Internal

Control

Signals

The following signals can be output to the Pulse Catch and
Counter Module from the ladder logic program.

1) Counter enable:

External input is enabled on the Pulse Catch and Counter
Module while this signal is ON. A signal can be set for every
external input circuit.

2) Clear:

The count from the counter function will be cleared when this
signal turns ON.

Monitor

Function

The following signal can be monitored from the ladder logic
program.

Carry:
This signal stays ON for only a few scans after the count passes
FFFF(h) and returns to 0 if the counter function is in Absolute
Mode.

4