Function – Yaskawa MEMOCON GL120 User Manual

Page 223

Advertising
background image

4.4 Communications Modules

— 4-167 —

If an error occurs either in the Module or in the Uniwire System, the READY, ERR1, ERR2 and
ERR3 indicators will operate as follows:

Type

Error

READY

ERR1

ERR2

ERR3

Remarks

Module ROM error

Not lit

Lit

Not lit

Not lit

Checked when power

i

d ON

error

RAM error

Not lit

Not lit

Lit

Not lit

p

is turned ON.

Internal watchdog timer error

Not lit

Not lit

Not lit

Lit

Checked all the time.

Switch setting error

Lit

Lit

Lit

Not lit

Checked when power

is turned ON.

Unwire

D and V24 short-circuited.

Lit

Lit

Not lit

Not lit

Checked all the time.

system

error

D and G short-circuited, or D and G

connection reversed.

Lit

Not lit

Lit

Not lit

End Unit error or D line disconnected

Lit

Not lit

Not lit

Lit

H-System error

Lit

Lit

Not lit

Lit

2. Function

1) The Uniwire (H) I/F is an interface module compatible with the Uniwire System

manufactured by the NKE Corporation to reduce wiring. The Uniwire (H) I/F has the
following main functions.

• Communications with Uniwire System I/O Terminal Units

• Address detection of I/O Terminal Units with errors (for H-System)

• Notification to the CPU Module of information on I/O Terminal Units for which errors

have been detected (for H-System)

2) Interface Function

The Uniwire (H) I/F can be set for either a Normal System or a H-System. Both Normal
System and H-System I/O Terminal Units are available. Contact the NKE Corporation for
details on I/O Terminal Units.