6.2

I/O Modules

— 6-17 —

2) 200-to 240-VAC 16-point Input Module

Table 6.5 Specifications of the 200-to 120-VAC 16-point Input Module

Item

Specification

Name

200- to 240-VAC 16-point Input Module

Model Name

AC200IN-16P

Model No.

JAMSC-120DAI74309 (EN standards)

Rated Voltage

200 to 240 VAC

Maximum Allowable Voltage

264 VAC

Rated Frequency

50/60 Hz

Allowable Frequency Range

47 to 63 Hz

Inrush Current

320 mA

Rated Current

7 mA (at 200 VAC, 50 Hz)

Input Impedance

28.6 kΩ (at 200 VAC, 50 Hz)
23.1 kΩ (at 200 VAC, 60 Hz)

Standard Operating Ranges

ON voltage range: 159 to 264 VAC
OFF voltage range: 40 VAC max.

Input Type

AC type 2 (according to IEC1131-2)

Input Delay Times

OFF to ON: 20 ms max.
ON to OFF: 35 ms max.

Number of Commons

2

Number of Inputs per Common

8 points/common

Input Power Supply per Common

Different power supply phases cannot be connected for

each common.

External Connections

Removable terminal block with M3 screw terminals

Number of Inputs

16

Input Signal Indication

Indicator for each point; lit when input is ON.

Status saved in internal logic.

Status Indication

ACTIVE: Lits during input processing

Insulation Method

Photocoupler

Dielectric Strength

1,500 VAC for 1 min or 1,800 VAC for 1 s between input

terminals and internal circuits and between all input

commons

Insulation Resistance

100 MΩ min. (room temperature and humidity) between

input terminals and ground (via 500-VDC insulation

resistance meter)

External Power Supply

200 to 240 VAC supplied to signals

Derating Conditions

None

Internal Current Consumption

90 mA max. at 5 VDC (with all points ON)

Maximum Heating Value

3.5 W

Hot Swapping (Removal/Insertion

under Power)

Permitted

Approximate Mass

250 g

External Dimensions

40.3 x 130 x 103.9 mm (W x H x D)