4.6 Special Purpose Modules

— 4-235 —

2) Performance Specifications

The following table shows the performance specifications of the High-speed Counter
Module.

Table 4.98 Performance Specifications of High-speed Counter Module

Items

Specifications

Number of Counter Circuits

1

Pulse

Count

Specifica-

tions

Pulse Input

System

D

There are four different types of pulse input systems:

1) Sign + pulse, 1X

2) A- and B-phase pulses, 1X

3) A- and B-phase pulses, 2X

4) A- and B-phase pulses, 4X

D

Using the ladder program, set the initial setting of the pulse input method as the “pulse
input mode.”

Maximum

Count Speed

1) 1X: 200 Kpps

2) 2X: 400 Kpps

3) 4X: 800 Kpps

Count Width

1) Using the ladder program, set the initial setting of the pulse count range as the “count

width.”

2) The setting range is between 0 and 16,777,215 (decimal).

Pulse Input

Voltage

1) Use any of the following pulse input voltages: 3, 5, 12 and 24 VDC.

2) The connection methods of the encoder cable to field wiring terminals differ according

to the pulse input voltage.

Pulse Transfer

Circuit

1) Use any of the following pulse types: open collector output, TTL output, differential

voltage output.

2) For an open-collector output, external power (5/12/24 VDC, 10/20 mA) must be

supplied.

Internal

Control Signal

The following signals can be output to the High-speed Counter Module from the ladder
program.

1) Count enable:

The High-speed Counter Module can count pulses while this signal and the external
count enable signal are both ON.

2) Current position reset:

The current position of High-speed Counter Module can be reset by turning ON this
signal.

External

Control Signal

D

The following signals can be input to the High-speed Counter Module from limit switches
or other external devices.

1) External count enable :

The High-speed Counter Module can count pulses while this signal and the count
enable signal are both ON.

2) External current position reset:

The current position of High-speed Counter Module can be reset by turning ON this
signal.

D

Input circuit specifications: 12/24 VDC, photocoupler isolation, 2.5 mA/5 mA.

4