Yaskawa MEMOCON GL120 User Manual

Page 152

Advertising
background image

System Components: Functions and Specifications

4.3.6 Using CPU Modules 3 (For CPU10) cont.

— 4-96 —

5) Setting Pin 1

a) Pin 1 is used to set communications parameters for MEMOBUS port 2. Set it to meet

the requirements of your system.

Table 4.37 Setting Communications Parameters for MEMOBUS Port 1

Pin 1

Function

ON

Sets communications mode of MEMOBUS port 1 to RTU and sets the

communications parameters for the MEMOBUS port 1 to the RTU mode defaults

shown below:
1) Slave address: 1

2) Baud rate:

9,600 bps

3) Parity check:

Yes

4) Parity:

Even

5) Stop bits:

1

6) Data bit length:

8

7) Delay time:

0 ms

OFF

Enables the user to define and set the communications mode and

communications parameters for the MEMOBUS port 1 through a programming

device (Programming Panel, personal computer, etc.).

b) A setting example of pin 1 is shown below.

(1) When the DIP switch pin 1 is set as shown in the diagram on

the right, the communications parameters of MEMOBUS
port 1 are set to the RTU mode defaults shown below:

Communications Mode: RTU
Communications Parameters

Slave address: 1
Baud rate:

9,600 bps

Parity check:

Yes

Parity:

Even

Stop bits:

1

Data bit length: 8
Delay time:

0 ms

(2) When connecting a Programming Panel to the CPU10 Module, the communica-

tions parameters must match the above values (except the delay time).

4

A

EXAMPLE

"