System Components: Functions and Specifications

4.4.3 Remote I/O Receiver Module

— 4-112 —

If a status error occurs, the READY indicator will go off and the RMT ERR indicator will flash
as described in the following table.

Type of Error

RMT ERR Indication

ROM error

RMT ERR will flash continuously.

RAM error

RMT ERR will flash twice, go off for 1 s, and then repeat the cycle.

ASIC error

RMT ERR will flash three times, go off for 1 s, and then repeat the cycle.

Watchdog timer error

RMT ERR will flash four times, go off for 1 s, and then repeat the cycle.

2. Function

The Remote I/O Receiver Module functions as a slave station in a Remote I/O System
using coaxial cable as the transmission cable.

3. Specifications

The specifications of the Remote I/O Receiver Module are shown in the following table.

Table 4.46 Specifications of Remote I/O Receiver Module

Item

Specifications

Model Name

RIOR-COAX

Model No.

JAMSC-120CRR13100

Internal Current Consumption

800 mA

Maximum Heating Value

4.0 W

Hot Swapping (Removal/Insertion

Under Power)

Permitted

Approximate Mass

300 g

External Dimensions

Width:

1

40.3 mm

Height: 130 mm

Depth: 103.9 mm

Remote I/O Port Specifications

Topology

(Communications

Network)

Bus

Media Access Control

Method

Multi-drop (1: n communications)

Media

(Transmission Medium)

Coaxial cable (75Ω)

Modulation Method

Base band

Encoding Method

Manchester code

Baud Rate

Choose from 0.5/1/2/4 Mbps

Transmission Distance

Transmission distance varies according to the baud rate

and specifications of coaxial cable. If, for example, the

baud rate is 4 Mbps and 12C-5AF Coaxial Cable is used,

it is possible to transmit up to 1 km max.

Number of Stations

15 max. (Up to 15 Remote I/O Receiver Modules can be

connected)

Error Measures (RAS)

Automatic parallel off and malfunctioning station recovery

Synchronization Method

Frame

Communications Format

Conforms to HDLC.

Insulation Method

Pulse transformer

Connector

BNC connector

4

Advertising