5.1 Designing the Control Panel
— 5-15 —
3) When the Modules shown in Table 5.5 are installed in a control panel, the depth of the
control panel necessary to mount a Module (dimension D) is as follows:
Dimension D = (depth dimensions of the module) + (cable connection length) mm
Refer to Table 5.5 and examples beginning on page B-16.
Table 5.5 Module Mounting Depth
Name
Depth of Module (mm)
Depth for Connection
Cable (mm)
Module
Mounting
Depth (mm)
Battery Module
63
85
Approx. 148
MEMOBUS PLUS Hub
Module
45
146.9
Approx. 192
2000-series Modem
Module
94
75
Approx. 175
*1
*1: Includes the length of metal fittings (6 mm).