Yaskawa MEMOCON GL120 User Manual

Page 415

Advertising
background image

Installation and Wiring

5.3.3 Wiring Digital I/O Modules cont.

— 5-58 —

Example 2: Load Driving Power Supply for 100/200 VAC 16-point Output Module

Load driving power

supply(single-phase,

100/200 VAC, 50/60 Hz)

Fuse

Load

Fuse

Load

Output 1
Output 2
Output 3
Output 4
Output 5
Output 6
Output 7
Output 8

Common 1-1
Common 1-2

Output 9
Output 10
Output 11
Output 12
Output 13
Output 14
Output 15
Output 16

Common 2-1
Common 2-2

Figure 5.2 Load Driving Power Supply

B. DC Power Supply Specifications

1) As shown in Examples 1 and 2 later in this section, it is necessary to supply external DC

power (12/24 VDC) to the I/O Modules listed in the following table to power input signals
and drive loads:

Table 5.9 Digital I/O Modules Requiring External DC Power Supply

Name

Model No.

External Power Supply Specifications

12/24-VDC 16-point

Input Module

JAMSC-120DDI34300

Rated voltage: 12/24 VDC
Maximum permissible voltage: 30 VDC

12/24-VDC 32-point

Input Module

JAMSC-120DDI35400

Maximum permissible voltage: 30 VDC
Standard operating range:
Minimum ON voltage: 9 VDC

12/24-VDC 64-point

Input Module

JAMSC-120DDI36400

Minimum ON voltage: 9 VDC
Maximum OFF voltage: 5 VDC