3 specifications of power supply modules – Yaskawa MEMOCON GL120 User Manual

Page 66

Advertising
background image

System Components: Functions and Specifications

4.2.3 Specifications of Power Supply Modules

— 4-10 —

4.2.3 Specifications of Power Supply Modules

1. Specifications of PS10 (Model No. JRMSP-120CPS11300)

PS10 specifications are shown in the following table.

Table 4.3 Specifications of PS10

Item

Specifications

Input

Rated Voltage

100/200 VAC (Selectable)

p

Permissible Voltage Range

85 to 132 VAC or 170 to 264 VAC

Rated Frequency

50/60 Hz

Permissible Frequency

Range

47 to 63 Hz

Permissible Momentary Pow-

er Interruption Time

Less than one cycle. Momentary power interrup-

tion intervals must be 1 s min.

Wave Distortion Factor

10% or less

Power Consumption

1) At 100 VAC: 100 VA max.

2) At 200 VAC: 120 VA max.

Current Leakage

1) At 132 VAC: 1.4 mA max.

2) At 264 VAC: 2.8 mA max.

Inrush Current

1) At 132 VAC, cold start: 25 A max.

2) At 264 VAC, cold start: 50 A max.

No. of Phases

Single-phase

Output Char-

i i

Rated Voltage

5.1 VDC

p

acteristics

Rated Current

7.0 A

Fuse

Standard fusing glass tube fuse (250 VAC, 3.15 A)

Field Wiring Terminals

1) Equipped with three types of terminals: field

wiring terminals (AC1, AC2), filter ground
terminal (ACG), and protective ground terminal
(FG).

2) M4 Phillips screws are used for the terminals.

3) Use wire size 1.5 mm

2

(AWG16) to 2.5 mm

2

(AWG13) to connect to the terminals.

Hot Swapping

(Removal/Insertion Under Power)

Not permitted.

Maximum Heating Value

20 W

Approximate Mass

600 g

External Dimensions

Width:

1

81 mm

Height:

130 mm

Depth:

103.9 mm

4

Advertising
This manual is related to the following products: