System Components: Functions and Specifications

4.4.13 Ethernet Interface Module

— 4-200 —

If an error occurs, the READY indicator will go OFF and the ERROR indicator will light
or flash as described in the following table.

Type of

Error

ERROR Indicator Status

ROM error

The ERROR indicator will flash one time, go OFF for 1 s, and

then repeat the cycle.

RAM error

The ERROR indicator will flash two times, go OFF for 1 s, and

then repeat the cycle.

DPM error

The ERROR indicator will flash six times, go OFF for 1 s, and

then repeat the cycle.

Watchdog

timer error

The ERROR indicator will flash seven times, go OFF for 1 s, and

then repeat the cycle.

Other error

The ERROR indicator will flash eight times, go OFF for 1 s, and

then repeat the cycle.

2. Function

The Ethernet Interface Module functions as an interface for connecting to GL120 and
GL130 Ethernet Network Systems.