Yaskawa MEMOCON GL120 User Manual

Page 31

Advertising
background image

2.1

Overview of the MEMOCON GL120 and GL130

— 2-7 —

Item

CPU35

(DDSCR-

130CPU54110)

CPU30

(DDSCR-

130CPU54100)

CPU21

(DDSCR-

120CPU34110)

CPU20

(DDSCR-

120CPU34100)

CPU10

(DDSCR-

120CPU14200)

Maximum number

of coils, relays, etc.

1) When the number of data registers is the initial value, the following condition must be

met:
(Number of coils) + (Number of relays) ≤ 65,520.

2) The maximum value for each reference can be freely set within the above limit from the

Programming Panel (Unit: point (1 point = 1 bit)).

Item

Setting range

Setting

unit

Defaults

Example
1

Example
2

Coils

16 to 65,472

16

8,192 57,328 65,472

Link coils

0 to 4,096

1,024

2,048

2,048

0

MC coils

0 to 512

256

512

512

0

MC control coils

0 to 320

160

320

320

0

Input relays

16 to 65,472

16

1,024

4,096

16

MC relays

0 to 512

256

512

512

0

MC control relays

0 to 512

256

512

512

0

M code relays

0 to 192

96

192

192

0

Maximum capacity

of data register

1) When the number of coils and relays is the initial value, the number of words of holding

registers plus the number of words of constant registers plus the number of words of link
registers must not exceed 25,998.

2) The maximum value for each reference can be freely set within the above limit from the

Programming Panel (Unit: word (1 word = 16 bits)).

Setting range

Setting

unit

Defaults

Example
1

Example
2

Holding register

1 to 25,995

1

9,999 19,854 25,995

Constant register

1 to 4,096

1

4,096

4,096

1

Link register

0 to 4,096

1,024

2,048

2,048

0

2

Advertising
This manual is related to the following products: