background image

4.3 CPU Modules

— 4-27 —

3. Appearance of CPU35 (Model No. DDSCR-130CPU54110)

Built-in battery

DIP switch

Key switch

Rotary switch 1

MEMOBUS port

MEMOBUS PLUS port

Module description

(130CPU54110)

Color code (yellow)

LED area

Rotary switch 2

Module mounting screw

(Use M4 Phillips screwdriver.)

LED

Color

Indication when ON

READY

Green

CPU Module is normal.

RUN

Green

CPU Module is running.

MB+/ERR

Green

MEMOBUS PLUS port is transmitting/receiving

data normally.

Red

Transmitting/receiving error has occurred in

MEMOBUS PLUS port.

BAT ALM

Red

Voltage in the built-in battery in CPU Module is

running down.

ACTIVE

Green

Access to CPU Module from other Module is

possible.

TX/ERR

Green

MEMOBUS port is transmitting data normally.

/

Red

Transmitting/receiving error has occurred in

MEMOBUS port.

RX

Green

MEMOBUS port is receiving data normally.

MEM PRT

Green

Key switch has selected memory protect ON.

Figure 4.10 Appearance of CPU35

Note

Make sure to replace the battery in the CPU Module within two weeks after the BAT ALM indi-
cator lights (replacement battery: BR-2/3A-1).
Programs or data stored in the CPU Module or Motion Modules will be lost if replacement is
delayed.

4

RUN

READY

130 CPU 541 10

MB+/ERR

BAT ALM

ACTIVE
TX/ERR

RX
MEM PRT

LED area