Yaskawa MEMOCON GL120 User Manual

Page 67

Advertising
background image

4.2 Power Supply Modules

— 4-11 —

2. Specifications of PS05 (Model No. JRMSP-120CPS11100)

PS05 specifications are shown in the following table.

Table 4.4 Specifications of PS05

Item

Specifications

Input

Rated Voltage

100/200 VAC (Selectable)

p

Permissible Voltage Range

85 to 132 VAC or 170 to 264 VAC

Rated Frequency

50/60 Hz

Permissible Frequency

Range

47 to 63 Hz

Permissible Momentary Pow-

er Interruption Time

Less than one cycle. However, momentary power

interruption intervals must be more than 1 s.

Wave Distortion Factor

10% or less

Power Consumption

1) At 100 VAC: 60 VA max.

2) At 200 VAC: 75 VA max.

Current Leakage

1) At 132 VAC: 1.4 mA max.

2) At 264 VAC: 2.8 mA max.

Inrush Current

1) At 132 VAC, cold start: 25 A max.

2) At 264 VAC, cold start: 50 A max.

No. of Phases

Single-phase

Output char-

i i

Permissible Voltage Range

5.1 VDC

p

acteristics

Rated Current

3.0 A

Fuse

Standard fusing glass tube fuse (250 VAC, 2 A)

Field Wiring Terminals

1) Equipped with three kinds of terminals: field

wiring terminals (AC1, AC2), filter ground
terminal (ACG), and protective ground terminal
(FG).

2) M4 Phillips screws are used in each terminal.

3) Use wire size 1.5 mm

2

(AWG16) to 2.5 mm

2

(AWG13) to connect terminals.

Hot Swapping

(Removal/Insertion Under Power)

Not permitted

Maximum Heating Value

10 W

Approximate Mass

350 g

External Dimensions

Width:

1

40.3 mm

Height:

130 mm

Depth:

103.9 mm

4