System Components: Functions and Specifications

4.4.9 Uniwire H-system Interface Module cont.

— 4-172 —

4) Example of H-System Configuration

The following diagram shows an example of the system configuration when a Uniwire (H) I/F
is used in H-System 200 m mode.

PS05:

AC Input Power Supply Module (3 A)

CPU20:

CPU Module (16 KW)

UNI(H):

Uniwire H-System Interface Module

DI:

12/24-VDC 16-point Input Module

DO:

12/24-VDC 16-point Output Module

MB12:

12-slot Mounting Base

HB-4:

Branching Unit

PTV-H04R: Address-incorporated Power Terminal Unit

(200 VAC, 2.0 A, relay contact outputs, 4 circuits)
PTV-H16T:Address-incorporated Power Terminal Unit

(24 VDC, 200 mA, transistor outputs with short-circuit

protection, 16 circuits)
STV-H04T:Address-incorporated Sensor Terminal Unit

(24 VDC, photocoupler isolation, 4 circuits)
STV-H16T:Address-incorporated Sensor Terminal Unit

(24 VDC, photocoupler isolation, 16 circuits)

24-VDC sensors

24-VDC, 200-mA loads

200-VAC, 2.0-A

loads

DI

UNI

DI

DI

M

P

CPU20

DO DO

DI

DI

Local channel/Rack 1 (CPU Rack)

Address-incorporated

Output Units

(4 points ¢ 2 Units)

HB-

4

P120C

Programming

Panel

DC power

supply

(24 VDC)

W0203-02

PS

05

DO

For Uniwire

transmissions

#0

PTV-

H04R

MB12

8 points

Transmission cable

Address-incorporated

PTV-H16T

#8

16 points

Address-incorporated

Input Units (4 points × 3 Units)

#24

12 points

24-VDC sensors

16 points

Transmission cable

(Total length: 200 m)

Uniwire System address:

#0, #4, #8, #24,

#28, #32, #36.

Output Unit (16 points ¢ 1 Unit)

(H)

Transmission cable

PTV-

H04R

HB-

4

HB-

4

STV-

H04T

Transmission cable

STV-

H04T

STV-

H04T

Address-incorporated

STV-H16T

#36 Input Unit (16 points ¢ 1 Unit)

Transmission cable

HB-

4

#4

#28

#32

Figure 4.48 H-System Configuration Example