6.1

Power Supply Modules

— 6-5 —

6.1.3 Functions and Specifications of Power Supply Modules

Low Voltage Directives PS05 and PS10 specifications are shown in the following table.

Table 6.2 Specifications of PS05 and PS10

Item

Specifications

Model Name

PS05

PS10

Model No.

JRMSP-120CPS11109

JRMSP-120CPS11309

Input

Rated Voltage

100 to 120 VAC or 200 to 240 VAC (Selectable)

p

Permissible Voltage Range 85 to 132 VAC or 170 to 264 VAC
Rated Frequency

50/60 Hz

Permissible Frequency

Range

47 to 63 Hz

Permissible Momentary

Power Interruption Time

Less than one cycle. Momentary power interruption intervals

must be 1 s.

Wave Distortion Factor

10% or less

Power Consumption

1) At 100 VAC: 60 VA max.

2) At 200 VAC: 75 VA max.

1) At 100 VAC: 100 VA max.

2) At 200 VAC: 120 VA max.

Current Leakage

1) At 132 VAC: 1.4 mA max.

2) At 264 VAC: 2.8 mA max.

Inrush Current

1) At 132 VAC, cold start: 25 A max.

2) At 264 VAC, cold start: 50 A max.

No. of Phases

Single-phase

Output

Charac-

Rated Voltage

5.1 VDC

Charac-

teristics

Rated Current

3.0 A

7.0 A

Fuse

Standard fusing glass tube

fuse (250 VAC, 2.0 A)

Standard fusing glass tube

fuse (250 VAC, 3.15 A)

Field Wiring Terminals

1) Equipped with three types of terminals, field wiring

terminals (AC1, AC2), filter ground terminal (ACG), and
functional earth terminal (FE).

2) M4 Phillips screws are used for the terminals.

3) Use wire size 1.5 mm

2

(AWG16) to 2.5 mm

2

(AWG13) to

connect to the terminals.

Hot Swapping

(Removal/Insertion Under Power)

Not permitted.

Maximum Heating Value

10 W

20 W

Approximate Mass

350 g

600 g

External Dimensions

Width:

40.3 mm

Height:

130 mm

Depth:

103.9 mm

Width:

81 mm

Height:

130 mm

Depth:

103.9 mm

6

Advertising
This manual is related to the following products: