241 — 3. specifications – Yaskawa MEMOCON GL120 User Manual

Page 297

Advertising
background image

4.6 Special Purpose Modules

— 4-241 —

3. Specifications

1) Hardware Specifications

The following table shows the hardware specifications of the Pulse Catch Module.

Table 4.99 Hardware Specifications of Pulse Catch Module

Item

Specifications

Voltage Used

12 VDC

24 VDC

Name

Pulse Catch and Counter Module

Module Name

COUNTER-16CH

Model No.

JAMSC-120RDI34400

Rated Voltage

12/24 VDC

Maximum Permissible

Voltage

30 VDC

Input Type

Sourcing/sinking

Rated Current

5.0 mA

10.5 mA

Input Impedance

2.2 kΩ

Standard Operating

Range

Minimum ON Voltage:

9 VDC

Maximum OFF Voltage: 5 VDC

Input Type

Does not conform to JIS B 3501.

DC type 2 according to JIS B

3501.

Number of Commons

1

Input Points per Common

16 points per common

External Connections

40-pin connector: 1

Connector model: FCN-365P040 (made by Fujitsu Ltd.)

Input Points

16 points (when using pulse catch and counter functions together)

Input Signal Indicators

Light for each point that is ON, internal logic

Isolation Method

Photocoupler isolation

External Power Supply

For signals: 12 VDC

For signals: 24 VDC

Derating Conditions

None

Internal Current

Consumption

5 VDC, 200 mA (when all points are ON)

Maximum Heating Value

6 W

Hot Swapping

Permitted.

Approximate Mass

300 g

External Dimensions

40.3 ¢ 130.0 ¢ 103.9 mm (W x H x D)

4

Advertising