4.1 General Specifications

— 4-3 —

4.1

General Specifications

This section provides the general specifications of the GL120 and GL130.

The general specifications of the GL120 and GL130 are shown in the following table.

Table 4.1 General Specifications

Item

Specifications

Dielectric Strength

1) Between the primary side and the grounding or

between the primary side and the secondary side:
Detected current 10 mA max. with 1,500 VAC for 1
minute or 1,800 VAC for 1 s.

2) Between the secondary side and the grounding:

Detected current 30 mA max. with 500 VAC for 1
minute or 550 VAC for 1 s.

Insulation Resistance

1) 10 MΩ min. between the primary side and the

grounding or between the primary side and the
secondary side (via the 500-VDC insulation
resistance meter)

2) 100 MΩ min. between the secondary side and the

grounding (via the 500-VDC insulation resistance
meter)

Environment

Conditions

Ambient Operating

Temperature

0 to 60 _C

Co d o s

Ambient Storage

Temperature

−25 to 85 _C (except batteries)

Ambient Operating

Humidity

30% to 95% RH (with no condensation)

Ambient Storage

Humidity

5% to 95% RH (with no condensation)

Pollution Level

Pollution level 1 according to JIS B 3501

Corrosive Gas

No corrosive gas

Operating Altitude

Less than 2,000 m above sea level

Mechanical

Operating

Conditions

Vibration Resistance

10 to 57 Hz with half-amplitude of 0.075 mm

57 to 150 Hz with fixed acceleration of 9.8 m/s

2

10 sweep times each in X, Y, and Z directions

(according to JIS B 3502)/(sweep time: 1 octave/min)

Shock Resistance

Peak acceleration of 147 m/s

2

twice for 11 ms in X, Y,

and Z directions (according to JIS B 3502)

Electrical

Operating

Conditions

Noise Resistance

1,500 V in either normal or common mode with pulse

widths of 100 ns/1 µs and rise time of 1 ns

(according to JIS B 3502) (with impulse noise simulator)

Installation

R

i

Ground

Ground to 100 Ω or less

Require-

ments

Configuration

Building-block, wall-mounted or DIN track-mounted

ments

Cooling Method

Natural cooling

4