Yaskawa MEMOCON GL120 User Manual

Page 198

Advertising
background image

System Components: Functions and Specifications

4.4.6 MEMOBUS Modules (RS-422) cont.

— 4-142 —

Example 4
Connecting ASCII Device (1:1 Communications)

PS10:

Power Supply Module (7 A)

CPU20:

CPU Module (16 KW)

MEM422: MEMOBUS Module (RS-422)

DI:

12/24-VDC 16-point Input Module

DO:

12/24-VDC 16-point Output Module

MB10:

10-slot Mounting Base

Communications by COMM instruction

DI

Set MEMOBUS port of

MEMOBUS Module thus:

D

Combined
master/slave port

D

transparent mode

Data input

M

PS10

DI

MEM

422

M

M

P

MB10

Slot No.

Local channel
Rack 1 (CPU Rack)

CPU20

1

2

3

4

5

6

7

8

9

10

DI

DO DO

Communications by COMM instruction

M

Bar code reader

Needs to be equipped with

RS-422 interface

Electronic scale

Shielded twisted

pair cable

(500 m max.)

Data input

Needs to be equipped with

RS-422 interface

Figure 4.36 Connecting ASCII Devices (1: 1 Communications)

d) The connector for a MEMOBUS port is a D-sub connector (9-pin, female). The con-

nector pin arrangement and signal names are shown in the following table:

Table 4.60 Pin Arrangement and the Signal Names

Pin No.

Symbol

Signal Name

1

PGND

Protective ground

2

TXD

Transmission data

3

RXD

Reception data

4

RXDRT

Receiver termination resistance:120 Ω

5

Not used

6

RXD

Reception data inversion

7

SGND

Signal ground

8

TXRD

Sender termination resistance:120 Ω

9

TXD

Transmission data inversion

4

A

EXAMPLE

"

Advertising
This manual is related to the following products: