4.4 Communications Modules

— 4-185 —

b) The maximum numbers of points and registers that can be allocated for the M-NET

Module master (total of ports 1 and 2) are as follows:

(1) The maximum numbers of I/O points and registers that can be allocated for the

M-NET Module master (total of ports 1 and 2) are 64 input bytes and 64 output
bytes.

(2) Digital references (input relays) and register references (input registers) are allo-

cated to the master station in Y mode as input references. Input relays and input
registers can be allocated together.

• Digital input references (input relays)

≤ 256 points

• Register input references (input registers)

≤ 15 registers

(3) Digital references (input relays) are allocated to the master station in T mode as

input references. Input registers cannot be allocated.

• Digital input references (input relays)

≤ 256 points

(4) Digital references (output coils) and register references (output registers) are al-

located to the master station in Y mode as output references. The allocation of
output coils and output registers can be mixed.

• Digital output references (output coils)

≤ 256 points

• Register output references (output registers)

≤ 15 registers

(5) Digital references (output coils) are allocated to the master station in T mode as

output references. Output registers cannot be allocated.

• Digital output references (output coils)

≤ 256 points

c) The number of M-NET Modules that can be connected depends on the number of the

above I/O references that can be allocated by the CPU Module.

2) Installation Locations

a) An M-NET Module can be mounted to any slot of the Mounting Base of any Rack. It

will occupy one slot.

b) The following diagram shows where to mount an M-NET Module.

4