Yaskawa MEMOCON GL120 User Manual

Page 267

Advertising
background image

4.4 Communications Modules

— 4-211 —

Table 4.88 Specification of Optical/Electrical Conversion Module

Items

Specifications

Model Name

O/E CONVERT

Model No.

JAMSC-120NAH93500 (cascade connections with H-PCF cable)

JAMSC-120NAH93510 (cascade connections with quartz optical fiber cable)

JAMSC-120NAH93520 (duplex connections with H-PCF cable)

JAMSC-120NAH93530 (duplex connections with quartz optical fiber cable)

External

Dimensions

Width: 40.3 mm

Height: 130 mm

Depth: 103.9 mm

Approximate

Mass

300 g

Internal Current

Consumption

430 mA

Maximum

Heating Value

2.5 W

Hot Swapping

(Removal/

Insertion Under

Power)

Permitted

Mounting

Location

Any slot of any Rack.

Electrical Port

S

ifi

i

Relay Method

Half duplex

Specifications

Topology

(Communications

Network)

Bus

Media (Transmission

Medium)

Coaxial cable (75 Ω )

Encoding Method

Manchester code

Baud Rate

Choose from 0.5, 1, 2, and 4 Mbps

Transmission Distance

Transmission distance varies according to the

baud rate and specifications of coaxial cable. If,

for example, the baud rate is 4 Mbps and

12C-5AF Coaxial Cable is used, it is possible to

transmit up to 1 km max.

Number of Stations

32 stations max. A maximum of 32 PC Link or

Remote I/O Driver and Receiver Modules can be

connected (including the local station). The

electrical port of the Optical/Electrical Conversion

Module should be the end station.

Communications Format Conforms to HDLC
Maximum Packet Length 256 words (16-bit words)
Max. Preamble Loss

3.5 bits per station

Max. Transmission

Delay

3.5 bits per station

Insulation Method

Pulse transformer

Connector

BNC connector

Model: BNC-P-3-Ni-CAu (description: BNC-P-3)

Terminator

Built-in (75 Ω)

4

Advertising
This manual is related to the following products: