Yaskawa MEMOCON GL120 User Manual

Page 153

Advertising
background image

4.3 CPU Modules

— 4-97 —

6) Setting Pin 2

a) Pin 2 is used to set communications parameters for MEMOBUS port 2. Set this pin to

meet the requirements of your system.

Table 4.38 Setting Communications Parameters for MEMOBUS Port 2

Pin 2

Function

ON

Sets communications mode of MEMOBUS port 2 to RTU and sets the

communications parameters for the MEMOBUS port 2 to the RTU mode defaults

shown below:
1) Slave address: 1

2) Baud rate:

9,600 bps

3) Parity check:

Yes

4) Parity:

Even

5) Stop bits:

1

6) Data bit length:

8

7) Delay time:

0 ms

OFF

Enables the user to define and set the communications mode and

communications parameters for the MEMOBUS port 2 through a programming

device (Programming Panel, personal computer, etc.).

7) Setting Pins 3 and 4

a) Pins 3 and 4 are used to set communications parameters for MEMOBUS port 2. Set

them to meet the requirements of your system.

Table 4.39 Setting Communications Parameters for MEMOBUS Port 2

Pin 3

Pin 4

Function

ON

ON

1) Sets MEMOBUS port 2 as a master port.

2) Master communications (COMM instruction) will be

enabled for MEMOBUS port 2 when the CPU10 Module
is in RUN mode and the communications mode will be
set to Transparent Mode.

3) Slave communications will be enabled when the CPU10

Module is in STOP mode.

OFF

1) Sets MEMOBUS port 2 as a master port.

2) Master communications (COMM instruction) will be

enabled for MEMOBUS port 2 when the CPU10 Module
is in RUN mode and the communications mode will be
set to MEMOBUS Mode.

3) Slave communications will be enabled when the CPU10

Module is in STOP mode.

OFF

ON or OFF

Sets MEMOBUS port 2 as a slave port. Master

communications will be disabled.