189 — 2. function, Specifications – Yaskawa MEMOCON GL120 User Manual

Page 245

Advertising
background image

4.4 Communications Modules

— 4-189 —

2. Function

The YENET 1600-D Module functions as station of a YENET 1600-D System.

3. Specifications

1) Module Specifications

Table 4.77 Specifications of YENET 1600-D Module

Item

Specifications

Name

YENET 1600-D Module

Model Name

YENET 1600-D

Model No.

JAMSC-120NDN31110

External dimensions

Width: 40.3 mm

Height: 130 mm

Depth: 103.9 mm

Approximate Mass

300 g

Internal Current Consumption

250 mA

Maximum Heating Value

1.9 W

Hot Swapping

(Removal/Insertion Under

Power)

Permitted

External Power Supply Voltage

For communication: 24 VDC, 25 mA

External Connections

Removable terminal block for field connections (5-pin with flange,

made by Phoenix Contact Co, model number MSTB2.5/5-STF-5.08)

Mounting Location

Any slot of any Rack

Communications

Port

S

Connection

Method

Multi-drop, T-branch (1:N)

o

Specifications

Baud Rate

500, 250, or 125 Kbps (selectable)

Transmission

Medium

Special 5-wire cable (2 signal lines, 2 power lines, 1 shield), or 3-wire

cable (separate power cable required)

Transmission

Distance

Baud Rate

Network Length

(Max.)

Drop Line

Length (Max.)

Total Drop Line

Length (Max.)

s a ce

500 Kbps

100 m

6 m

39 m

250 Kbps

250 m

6 m

78 m

125 Kbps

500 m

6 m

156 m

Node

Address

0 to 15

Number of

Units

Connected

63 max.

Status

Information

Can be monitored in Monitor Mode

Transmission

Error

Detection

CRC errors, duplicate node address check

2) I/O Specification

The YENET 1600-D Module operates in Master Mode or Slave Mode according to set-
tings made from the MEMOSOFT.

4

Advertising
This manual is related to the following products: