Installation and Wiring

5.3.3 Wiring Digital I/O Modules cont.

— 5-66 —

7) When using an insulation transformer for the primary side of DC voltage stabilizing power

supply, always make sure to separate the primary and the secondary coils. When using a
noise filter, also be sure to separate the primary and the secondary coils.

C. 64-point Digital I/O Module

1) There are 2 64-point Digital I/O Modules with connectors for external connections.

a) 12/24-VDC 64-point Input Module (Model No.: JAMSC-120DDI36400)

b) 12/24-VDC 64-point Output Module (Model No.: JAMSC-120DDO36410)

2) Use the following cables for the I/O signal wire to connect to the I/O Modules.

a) I/O signal cables manufactured by the customer

b) 64-point I/O Module cables W5410 manufactured by Yaskawa

3) Use the following electric cables and connectors to manufacture I/O signal cables to con-

nect to these Digital I/O Modules.

a) Cable size: 0.26 mm

2

(AWG23)

b) Module connector (provided as accessory)

• Connector: FCN-361J040-AU (soldered) (Fujitsu)

• Cover: FCN-360C040-B (Fujitsu)

4) When an W5410 64-point I/O Module Cable is used, select the appropriate cable from

the 4 cables shown in the following table:

Table 5.15 W5410 64-point I/O Module Cables

Item

Specifications

Name

W5410 Cable

Model Name

W5410-05

W5410-10

W5410-30

Model No.

JEPMC-W5410-05

JEPMC-W5410-10

JEPMC-W5410-30

Length (L)

0.5 m

1.0 m

3.0 m

Cable Specifications

Shielded cable of 40 conductors, corresponding to AWG24 (0.20 mm

2

)

Terminals Module side Connector fitted: FCN-363J-040

(FUJITSU LTD.)

FCN-360C040-B (FUJITSU LTD.)

FCN-363J-AU/R (FUJITSU LTD.)

External
device side

Loose wires: Wire length 100 mm with pin number label on each wire.