System Components: Functions and Specifications

4.3.2 CPU Modules: Functions and Models cont.

— 4-32 —

Model Name

CPU35

CPU30

CPU21

CPU20

CPU10

Maximum I/O

Points/Regis-

Digital I/O points

1,024 points max. (1 point: 1 bit) *1

4,096 points max. (1 point:

1 bit) *1

o s/ eg s

ters

I/O registers

512 registers max. (1 register: 16 bits) *2

Local I/O

1) Number of channels: 1

2) Number of Racks: 4 Racks max. including CPU Rack.

3) Number of mountable I/O Modules: 54 max.

The total number of remote I/O points and registers must meet the above
conditions *1 and *2.

Remote I/O

1) Number of channels: 2

2) Number of stations per channel: 15

3) Number of Racks per channel: 4 Racks max.

4) Number of I/O points per station:

(Digital input points ÷ 8) + (Input registers × 2) ≤ 512 bytes

(Digital output points ÷ 8) + (Output registers × 2) ≤ 512 bytes

The total number of local I/O points and registers must meet the above
conditions *1 and *2.

Maximum Capacity of Data Register

1) When the number of coils and relays is the default value, the following

condition must be met:
(Number of holding register words) + (Number of constant register words) +
(Number of link register words) ≤ 25,998

2) The maximum value of each reference can be freely set within the above limit

and the following ranges using MEMOSOFT.

Unit: word (1 word = 16 bits)

Register

Setting

Range

Setting Unit

Default

Value

Example 1

Example 2

Holding

registers

1 to

25,995

1

9,999

19,854

25,995

Constant

registers

1 to 4,096 1

4,096

4,096

1

Link

registers

1 to 4,096 1,024

2,048

2,048

0

4