background image

4.4 Communications Modules

— 4-197 —

c) The setting of the rotary switches is effective when the reset switch is pressed, or

when the power is turned ON to Power Supply Module of the Rack where the YENET
1600-D Module is mounted.

d) The node address is set to between 0 and 15 (0 and F in hexadecimal). The following

table shows how to set the node address.

Table 4.81 Setting the Node Address

Example

Settings of Node Address

Node Address

Rotary Switch

Rotary switch

NODE
ADDRESS

1 to 15

0 to F

Note

(1) Do not use the same node address for more than one node within the same commu-

nications circuit. If this occurs, nodes with the same address will not be able to commu-
nicate normally.

(2) The rotary switch settings will become effective by pressing the reset switch, or turning

ON the power to the Power Supply Module of the Rack to which the YENET 1600-D
Module is mounted.

8) Reset Switch

a) Press the reset switch in the following cases:

(1) When you have changed the setting of the DIP switch.

(2) When you have changed the setting of the rotary switches.

(3) When errors have occurred.

b) When the reset switch is pressed, communications between the YENET 1600-D

Module and other YENET 1600-D Modules are interrupted. Communications restart
when the switch is released.