Yaskawa MEMOCON GL120 User Manual

Page 84

Advertising
background image

System Components: Functions and Specifications

4.3.1 Appearance of CPU Modules cont.

— 4-28 —

4. Appearance of CPU21 (Model No. DDSCR-120CPU34110)

Built-in battery

DIP switch

Key switch

Rotary switch 1

MEMOBUS port

MEMOBUS PLUS port

Module description

(120CPU34110)
Color code (yellow)

LED area

Module mounting screw

(Use M4 Phillips screwdriver.)

Rotary switch 2

PC Card slot

LED

Color

Indication when ON

READY

Green

CPU Module is normal.

RUN

Green

CPU Module is running.

MB+/ERR

Green

MEMOBUS PLUS port is transmitting/receiving data

normally.

Red

Transmitting/receiving error has occurred in

MEMOBUS PLUS port.

CRD/BAT

Green

Lit:

CPU Module is accessing PC Card.

Flash: PC Card error has occurred in CPU Module.

Red

Voltage in the built-in battery in CPU Module is running

down.

ACTIVE

Green

Access to CPU Module from other Module is possible.

TX/ERR

Green

MEMOBUS port is transmitting data normally.

/

Red

Transmitting/receiving error has occurred in

MEMOBUS port.

RX

Green

MEMOBUS port is receiving data normally.

MEM PRT

Green

Key switch has selected memory protect ON.

Figure 4.11 Appearance of CPU21

Note

Make sure to replace the battery in the CPU Module within two weeks after the CRD/BAT
indicator lights red (replacement battery: BR-2/3A-1).
Programs or data stored in the CPU Module or Motion Modules will be lost if replacement is
delayed.

4

RUN

READY

120 CPU 341 10

MB+/ERR

CRD/BAT

ACTIVE
TX/ERR

RX
MEM PRT

LED area

Advertising
This manual is related to the following products: