System Components: Functions and Specifications

4.4.6 MEMOBUS Modules (RS-422)

— 4-136 —

When a status error has occurred, the READY, ERR1, and ERR2 indicators will operate as
shown in the following table:

Type of Error

READY

ERR1

ERR2

Remarks

ROM error

Flashes

Not lit

Not lit

Checked all the time.

RAM error

Not lit

Flashes

Not lit

Checked when power is turned ON.

Common memory error

Flashes

Flashes

Not lit

Checked when power is turned ON.

Watchdog timer error

Not lit

Flashes

Flashes

Checked all the time.

2. Function

1) The MEMOBUS Module (RS-422) is equipped with two MEMOBUS ports for RS-422

communications.

2) The MEMOBUS Module (RS-422) performs communications using RS-422 (master

communications or slave communications) through the MEMOBUS ports. The MEMO-
BUS protocol or any other protocol can be used for the communications protocol.

3) The features of the MEMOBUS Module (RS-422) are as follows:

a) The transmission distance can be extended up to 500 m without a modem.

b) Communications in 1:n format are possible without a modem: 1 master and up to 31

slaves.

4) The MEMOBUS Module (RS-422) can use either 2-line or 4-line communications.

Note

The maximum transmission distance and the number of slaves for 1:n communications vary
according to the specifications of connected communications devices.